125 KVA / 100 KW Kirloskar Diesel Generator on Rent  

125 KVA / 100 KW Kirloskar Diesel Generator on Rent

GENSET DETAILS

Prime Rating at rated rpm
125 KVA / 100 KW
Genset Model
KG1- 125WS
Frequency
50 Hz
Power factor
0.8 lagging
Voltage
415 3Ø V
Governing class
G3
Noise level
dBA < 75
Fuel Consumption
Load 100%
27.4 Ltrs/Hr
Load 75%
20.2 Ltrs/Hr
Load 50%
15.3 Ltrs/Hr
Fuel Tank Capacity
230 Ltrs
Dimensions (L x W x H)
3200 x 1300 x 1795 mm
Dry weight with Canopy
2090 Kg
Wet weight with Canopy
2290 Kg
Electrical Battery
12 Volts-DC

ENGINE DETAILS

Engine Model
4K1080TA G2
Rated output
114.7 kW
Rated output
156 HP
No. of cylinder
4
Cubic capacity
4.32 Ltrs
Bore x Stroke
105 x 125 mm
Rated Speed
1500 RPM
Aspiration
TA NA/TC/TA
Lube Oil change period
500 hrs.
Lube oil Sump Capacity
18 Ltrs
Coolant Capacity
21 Ltrs

ALTERNATOR DETAILS

Insulation Class
Class H
Alternator Efficiency
92.5 %
Max Voltage Dip at Full Load 0.8 pf Lag
< 20 % sec
Max Time to build up rated voltage at Rated RPM
< 5 sec provided engine reach the rated speed

PRIME RATTING AND STANDARD BY RATING

'Prime power' is designed for Unlimited hours, as compared to 'Emergency stand-by' designed for 200 hours in a year. Prime rated Gensets also permit 10% temporary overloading. Users need to carefully select the Genset rating to meet their requirement. KOEL offers Prime power as standard offer. Contact KOEL for stand-by ratings.

ENGINE CAPACITY DOES MATTER

Engine capacity (cc) plays a vital role in Genset performance. Higher engine capacity leads to a robust and stable Genset performance. Higher engine capacity also enables Genset to respond quickly & positively to sudden load additions.
Canopy features
  • Ease of Access and Serviceability
  • Aesthetically designed, weather and sound resistant enclosure
  • Insulation conforms to UL94-HF1 class for flammability
Controller features
  • Microprocessor based fully configured
  • Graphical bigger LCD display
  • Best in class monitoring and diagnostic
  • Integrable with AMF, synchronization & communication configurations
Engine features
  • O2E Series: Low emission, high efficiency engines
  • Compact, Robust and Rugged Design
  • 500 hours lube-oil change period
Alternator features
  • Best In Class Efficiency
  • Special Windings to Reduce Harmonics
  • Vacuum Pressure Impregnation and epoxy gel coating on winding
Monitoring features
Optional features

Koel's approach to meet revised CPCB norms1

Revised CPCB norms are aimed at protecting the environment by reducing Genset emissions and improving enission quality.These are some of the most stringent emission norms in the world

To meet the new norms, KOEL R & D team had choice of multiple technologies. While selecting the technology, KOEL laid significant emphasis on long term needs of users viz:

  • High reliability and durability of Gensets: Owing to extreme opera & ng conditions in India, preference has been given to robust configurations that have been running successfully for several years
  • Low running costs: An effort to reduce emissions tends to increase the running costs. KOEL has succeeded in achieving both in the same design.
  • Optimized fuel efficiency as per actual usage: KOEL Green Gensets are tuned to provide maximum fuel efficiency in the most common operating
Optional features